The hardware and bandwidth for this mirror is donated by METANET, the Webhosting and Full Service-Cloud Provider.
If you wish to report a bug, or if you are interested in having us mirror your free-software or open-source project, please feel free to contact us at mirror[@]metanet.ch.
title: “CNAIM” |
output: rmarkdown::html_vignette |
vignette: > |
% |
% |
% |
# Introduction
The green transition will require significant investment in utility infrastructure. Many countries have restrictive income caps or fixed tariffs that do not allow for investment to support the electrification of transport, heating and agricultural processes. Incentive-based revenue caps are the answer, and will likely be adopted in many countries over the next decade. This package allows regulators, data scientists and researchers to calculate and understand:
## Probability of failure
In CNAIM, the probability of failure (PoF) is modelled as the first three terms of a Taylor Series expansion of an exponential function.
\(\begin{align*} PoF =& K \cdot e^{(C \cdot H)} \\=& K \cdot \sum_{n=1}^\infty \frac{(C \cdot H)^n}{n!} \\\approx& K \cdot \left[1 + (C \cdot H) + \frac{(C \cdot H)^2}{2!} + \frac{(C \cdot H)^3}{3!}\right] \end{align*}\)
where
\(K\) scales the PoF to a failure rate that matches observed fault statistics
\(C\) describes the shape of the PoF curve
\(H\) is the health score based on observed and measured explanatory variables
The definition of a functional failure can be divided into three classes of failure modes:
Assuming a transformer:
Then we can call the function as follows:
pof <- pof_transformer_11_20kv(
hv_transformer_type = "6.6/11kV Transformer (GM)",
utilisation_pct = 55,
placement = "Indoor",
altitude_m = 75,
distance_from_coast_km = 20,
corrosion_category_index = 2,
age = 25,
partial_discharge = "Low",
oil_acidity = 0.1,
temperature_reading = "Normal",
observed_condition = "Default",
reliability_factor = "Default")
sprintf("The probability of failure is %.2f%% per year", 100*pof)
[1] "The probability of failure is 0.01% per year"
[2] "The probability of failure is 50.00% per year"
The only mandetory input variable is age; the rest have defaults, so you can call the function like:
pof <- pof_transformer_11_20kv(age = 55)
sprintf("The probability of failure is %.2f%% per year", 100*pof)
[1] "The probability of failure is 0.03% per year"
[2] "The probability of failure is 127.31% per year"
The CNAIM methodology’s second key element is the consequence of a failure. When combined with probability of failure, the consequences of failure can be used to derive the monetary network risk. Consequence of failure calculations are based on the same failure modes as probability of failure.
The consequences of failure can be divided into four:
The sub-consequences have an associated asset specific reference cost of failure based on the British DNOs’ experience and other objective sources. All reference costs are currently in 2012/2013 prices. The reference cost of failure for all sub-categories are scaled with respect to the specific conditions and locations of the individual asset.
Financial consequences of failure considers cost associated with replacement and repairs that returns the asset to its initial condition before the incident.
Safety consequences of failure considers the likelihood and the cost that a failure could be hazardous to a person or a worker including the likelihood that the failure could be fatal. The safety implications is taken from Electricity Safety, Quality and Continuity Regulations (ESQCR).
Environmental consequences of failure considers the cost of a potential oil spill and mitigation of the extremely potent greenhouse gas, sulfur hexafluoride.
Network performance consequences of failure considers the cost a failure imposes to the customers served by the by the asset and the number of interrupting minutes.
Assuming a transformer:
The financial reference cost of failure for a 6.6/11kV transformer is £7,739, which is scaled by the rated capacity measured in kVA and the accessibility. The financial consequences of failure are found using:
financial_cof <- f_cof_transformer_11kv(kva = 750, type = "Type B")
sprintf("The financial consequences of failure is GBP %.f", round(financial_cof))
[1] "The financial consequences of failure is GBP 13364"
The safety reference cost of failure for a 6.6/11kV transformer is £4,262, which is scaled by the location and the risk the transformer represents to the public. The function below is able to calculate the safety consequences of failure for switchgears, transformers and overhead lines:
safety_cof <- s_cof_swg_tf_ohl(type_risk = "Low",
location_risk = "Medium",
asset_type_scf = "6.6/11kV Transformer (GM)")
sprintf("The safety consequences of failure is GBP %.f", round(safety_cof))
[1] "The safety consequences of failure is GBP 4341"
The environmental reference cost of failure for a 6.6/11kV transformer is £3,171. The environmental consequences of failure calculation considers proximity to water courses, the asset’s rated capacity, and if the transformer is bunded or not. This function can calculate environmental consequences of failure for all types of transformers specified in CNAIM methodology:
environmental_cof <- e_cof_tf(asset_type_tf = "6.6/11kV Transformer (GM)",
rated_capacity = 750,
prox_water = 95,
bunded = "Yes")
sprintf("The environmental consequences of failure is GBP %.f", round(environmental_cof))
[1] "The environmental consequences of failure is GBP 1904"
The reference network performance cost of failure for a 6.6/11kV transformer is £4,862. This cost is scaled according to the number of customers connected to the transformer and kVA per customer. This function can calculate network consequences of failure for all assets with the exception EHV and 132kV asset:
network_cof <- n_cof_excl_ehv_132kv_tf(asset_type_ncf = "6.6/11kV Transformer (GM)",
no_customers = 750,
kva_per_customer = 1)
sprintf("The network performance consequences of failure is GBP %.f", round(network_cof))
[1] "The network performance consequences of failure is GBP 16286"
The overall consequences of failure in our example can found using:
cof_transformer <- cof(financial_cof, safety_cof, environmental_cof, network_cof)
sprintf("The consequences of failure is GBP %.f", cof_transformer)
[1] "The consequences of failure is GBP 35896"
The function adds the sub-consequences together to a total consequence of a failure. For the 6.6/11kV transformer described in this example, it is now possible to derive the monetary risk.
A quick way to find the consequences of failure for the 6.6/11kV transformer in this example is:
cof_short_cut <- cof_transformer_11kv(kva = 750, type = "Type B",
type_risk = "Low", location_risk = "Medium",
prox_water = 95, bunded = "Yes",
no_customers = 750, kva_per_customer = 1)
all.equal(cof_transformer, cof_short_cut)
[1] TRUE
source('fns_monetary_risk.R')
Once probability of failure and consequences of failure have been calculated for each asset, monetary risk is calculated as:
\(Risk = PoF \cdot CoF\)
Risk matrices for each asset class, along with cost-benefit analyses of interventions (reinvestment and maintenance) are submitted to the regulator, allowing utility and regulator to reach concensus on the right balance of cost and reliability.
Given an asset with a probability of failure = 0.08% per year and consequences of failure equal to £18,232, we can visualize and analyize which risk class this asset has with the following functions:
# Generate an empty 5x4 matrix
matrix_structure <- risk_matrix_structure(5,4,NA)
# Monetary risk for one asset
risk_coordinates <- risk_calculation(matrix_dimensions = matrix_structure,
id = "Transformer1",
pof = 0.08,
cof = 18232,
asset_type = "6.6/11kV Transformer (GM)")
risk_matrix_points_plot(matrix_structure,
dots_vector = risk_coordinates,
dot_radius = 4)
Given a population of assets within the same asset class, we can visualize how monetary risk is distributed with the following example:
# Generate an empty 5x4 matrix
risk_data_matrix <- risk_matrix_structure(5,4,NA)
risk_data_matrix$value <- sample(1:30,size=nrow(matrix_structure),replace = T)
risk_matrix_summary_plot(risk_data_matrix)
Sometimes it is desirable to create the matrix with non-linear intervals, since each interval represents a bin of CoF and PoF, bins which typically increase in size as the CoF and health scores increase. The inputs x_intervals
and y_intervals
should match the x and y dimensions of the risk matrix data frame, but can contain any values, since these are internally normalised to 1.
# Generate an empty 5x4 matrix
risk_data_matrix <- risk_matrix_structure(5,4,NA)
risk_data_matrix$value <- sample(1:30,size=nrow(matrix_structure),replace = T)
risk_matrix_summary_plot(risk_data_matrix,
x_intervals = c(0.1,0.1,0.1,0.2,0.3),
y_intervals = c(0.75,0.75,1,1.5))
Although the CNAIM standard specifies a rigid 5x4 matrix, it might be desirable to implement different size risk matrices. The CNAIM R package offers this flexibility. For example, to make a 4x4 matrix:
# Generate an empty 4x4 matrix
risk_data_matrix <- risk_matrix_structure(5,4,NA)
risk_data_matrix$value <- sample(1:30,size=nrow(matrix_structure),replace = T)
risk_matrix_summary_plot(risk_data_matrix)
These binaries (installable software) and packages are in development.